These notes come from reverse-engineering an Intelbras IONS-5K M5 with datalogger firmware WIFI-SV300.001.03.P002 on 2026-10-24. The library was tested against that real unit.

Identification

  • The datalogger web UI (GET /, a Vue + layui app) contains version:"WiNet_V1.0.0AB2020112601". That string marks it as a Sungrow WiNet-S sold under the Intelbras brand.
  • The WebSocket devicelist reports dev_model "IONS-5K M5", dev_code 9748 (0x2614) and dev_type 21 (string inverter).
  • Open ports: 80 (web UI), 443, 502 (Modbus TCP) and 8082 (WebSocket). Ports 502 and 8082 require no login.

WebSocket: ws://<ip>:8082/ws/home/overview

Requests and replies are JSON. Every reply has the shape {result_code: 1, result_msg, result_data: {service, ...}}. The server also pushes unsolicited notice messages, so match each reply on its service field.

Request Reply
{"service":"connect","token":""} Session token (no login)
devicelist with type:"0", is_check_token:"0" Inverters: serial, model, dev_id, link_status
real with dev_id 16 readings with I18N data_name keys
direct with dev_id Voltage and current for each MPPT
statistics / runtime Daily and total energy, current power, adjustable P/Q limits
state total_fault, total_alarm, wifi_conn_sts, cloud_conn_sts
fault Active fault list
real_battery, deviceInfo result_code 211/215 on this model (not supported)

Modbus TCP (port 502, unit 1)

This is the Sungrow SG-RS map. Addresses are 0-based (documentation address − 1), and 32-bit values are sent low word first.

Input registers (FC4)

Register Value Scale
4989–4998 Serial number (ASCII)
4999 Device type code
5000 Nominal power 0.1 kW
5002 Daily energy 0.1 kWh
5003 U32 Total energy kWh
5005 U32 Total running time h
5007 S16 Internal temperature 0.1 °C
5008 U32 Apparent power VA
5010/5011, 5012/5013 MPPT1 and MPPT2 voltage / current 0.1 V / 0.1 A
5016 U32 Total DC power W
5018 / 5021 Phase A voltage / current 0.1 V / 0.1 A
5030 U32 Active power W
5032 S32 Reactive power var
5034 S16 Power factor 0.001
5037 Work state (see WORK_STATES)
5038–5043 / 5044 Fault time / fault code
5070 Array insulation resistance kΩ
5112 Running time today min
5127 U32 Monthly energy 0.1 kWh
5143 U32 Total energy (high resolution) 0.1 kWh
5146 / 5147 Bus voltage / grid frequency 0.1 V / 0.01 Hz
5225 U32 Yearly energy (inferred) 0.1 kWh

Holding registers (FC3 read, FC6 write)

Register Value
4999–5004 Clock: year, month, day, hour, minute, second
5005 0xCF start, 0xCE stop
5006 Power limitation: 0xAA on, 0x55 off
5007 Power limit in 0.1 %

On this unit, a block read of the holding registers fails with exception 4 once it reaches register 5019.

Not verified

  • The yearly energy register (5225) is inferred. It read 6907 kWh while the Intelbras cloud showed 6842 kWh.
  • The control register values come from Sungrow's documentation and match what this unit reads back. They are exercised against a fake server in the tests.